Delivery time: 2 to 3 weeks (contact us)
Technical specifications |
|
Brand | EREA |
Commercial Order Number | 230TMHD3300/BTE |
EAN | 5414503103611 |
Class | Single-phase isolating transformer energy-efficient for application in medical purpose rooms - IP00 - Upri 230V // Usec 230V - Power 3300VA |
Primary voltage | 230 Vac |
Secondary voltage | 230 Vac |
Power | 3.3KVA |
Degree of protection | IP00 |
Dielectric Strenght (Vac) | 4500Vac |
Dielectric strength to mass (Vac)) | 2500Vac |
Standards |
EN 61558-2-15 EN 60748 |
Max. ambient temperature Ta (°C) | 50 °C |
Temperature class | B |
Application | For all applications in medical purpose rooms |
Protection class | Prepared for class I |
Voltage drop (dU%) | 2.2% |
Efficiency | 97.5% |
Pcu (W) | 70 W |
Po (W) | 14 W |
Size A x B x C (mm) | 240x200x310mm |
Size D (mm) | 150mm |
Size E (mm) | 158mm |
Weight | 45kg |
Primary connection | Screw terminals |
Secondary connection | Screw terminals |
Finish | Vacuum- and pressure- varnish impregnated |
Φ (mm) | 11mm |
Options |
|
On request | Special versions - PT100 temperature sensor |
Option Housing IP20 (accessory) | |
Option Housing IP23 (accessory) | |
Option Silent Block (accessory) | SILENT BLOCK 50 |